ALT Simplified Recommendations for Classroom Air Cleaning to Reduce the Risk of Far-Field Airborne Infectious Disease Transmission, Derived from ASHRAE Standards 241 & 62.1 TABLE. Educational Facility Type, followed by cfm/person, then ACH Libraries 40 2.7 Art classroom 40 5.3 Wood and metal shop 40 5.3 Computer lab 40 6.7 Media center 40 6.7 Science labs 40 6.7 University and college labs 40 6.7 Daycare, ages 4 and under 40 6.7 Classroom, ages 5-8 40 6.7 Classroom, ages 9+ 40 9.3 Music, theater, and dance 40 9.3 Lecture classroom 40 17.3 Multiuse assembly 40 26.7 Lecture hall, fixed seats 50 50.0 Note. cfm/person based on ASHRAE Standard 241. ACH derived from typical full-capacity person density estimates from ASHRAE Standard 62.1. Use the most comparable educational facility. If half or one-quarter capacity, prorate the ACH estimate accordingly. Calculations focus on reducing risk primarily of far-field transmission in rooms with well-mixed air, and masks remain needed...